Roof Sheathing & Shear Wall Inspection Checklist

Use this Roof Sheathing & Shear Wall Inspection Checklist to verify compliance with the 2018 International Residential Code (IRC).

Roof Sheathing & Shear Wall Inspection Checklist



Hold-Downs And Hardware

1. Are all floor-to-floor, wall-to-floor, and lateral straps and transfer connections installed per the approved plans?


Photo Comment

2. Are hold-downs not over-spalled beyond the manufacturer’s maximum allowance, with spalling greater than that allowed causing a reduction in load capacities (see manufacturer’s installation instructions) (MII)?


Photo Comment

3. Are hold-downs and straps attached properly per approved plans and/or manufacturer’s installation instructions (MII)?


Photo Comment

4. Are full-height studs required at strapping and hold-downs (MII)?


Photo Comment

5. Are multiple studs installed at strapping and hold-downs as required per the approved plan or manufacturer’s installation instructions (MII)?


Photo Comment

6. Are anchor bolts at garage walls and other areas not inspected during the underfloor inspection checked ?


Photo Comment

7. Is anchor bolt size and spacing per the shear wall schedule in the approved plans ?


Photo Comment

8. Is wall anchorage provided for all buildings in Seismic Design Categories D0, D1, and D2 and townhouses in Seismic Design Category C (? • Plate washers, a minimum of 0.229 inches by 3 inches by 3 inches in size, shall be provided between the foundation sill plate and the nut except where approved anchor straps are used. The hole in the plate washer is permitted to be diagonally slotted with a width of up to 3/16 inch larger than the bolt diameter and a slot length not to exceed 1- 3/4 inches, provided a standard cut washer is placed between the plate washer and the nut.


Photo Comment

9. For the braced wall panel method Portal Frame with Hold-downs (PFH), are strap-type hold-downs required per IRC ?


Photo Comment
Framing

1. Are framing member requirements for double 2x’s or 3x’s as shown on the approved plan and shear wall schedule checked?


Photo Comment

2. Have stud size, height, and spacing been confirmed?


Photo Comment

3. Is continuity maintained when an exterior wall (1-hour-rated) is within a 5-foot fire separation, and is this also verified at the time of foundation and framing inspections (WA Amendment)?


Photo Comment

4. Is cripple wall bracing, exterior and interior, per the requirements of (WA Amendment)?


Photo Comment
Permits And Plans

1. Is the job address posted in a visible location ?


Photo Comment

2. Are permits and approved plans on-site and accessible to the inspector?


Photo Comment

3. Is permit information correct, including address, permit number, description of work, etc. ?


Photo Comment

4. Are previous required building inspections approved ?


Photo Comment

5. Have all inspections, as required by the jurisdiction, received inspection approvals prior to cover, and have they been requested by the permit holder or agent ?


Photo Comment
Exterior Wall Sheathing And Braced Wall Panel

1. Is the exterior wall sheathing inspection completed before papering or siding ?


Photo Comment

2. Has the sheathing been verified to be the grade and thickness specified on the approved plans and/or engineering?


Photo Comment

3. Is the sheathing nailed per the shear wall/braced wall panel schedule on the approved plan, with common nail sizes used for vertical or horizontal diaphragms?


Photo Comment

4. Are sheathing edges and end joints blocked or occurring over horizontal or vertical framing members ?


Photo Comment

5. Are plate dimensions per shear wall schedule/approved plans ?


Photo Comment

6. Are plates fastened per the shear wall schedule/approved plans ?


Photo Comment

7. Are nailing/attachment requirements for required double 2x’s or 3x’s as shown on the approved plan and shear wall schedule checked ?


Photo Comment

8. Have stud size, height, and spacing been confirmed?


Photo Comment

9. Are fasteners at end joints not spaced greater than 6 inches on center and are firmly driven into the framing ?


Photo Comment

10. Do fastener heads or crowns not penetrate the outer veneer of plywood, and is loose sheathing attached to framing members using nails?


Photo Comment

11. Are fasteners for preservative-treated wood of hot-dipped zinc-coated galvanized steel, stainless steel, silicon bronze, or copper? Are staples of stainless steel? Are coating types and weights for connectors in contact with preservative-treated wood in accordance with the connector manufacturer's recommendations? In the absence of manufacturer's recommendations, is a minimum of ASTM A 653 type G185 zinc-coated galvanized steel, or equivalent, used?Exceptions: •One-half-inch diameter or greater steel bolts •Fasteners other than nails, staples, and timber rivets shall be permitted to be of mechanically deposited zinc-coated steel with coating weights in accordance with ASTM B 695, Class 55 minimum •Plain carbon steel fasteners in SBX/DOT and Zinc Borate preservative-treated wood in an interior, dry environment shall be permitted


Photo Comment

12. Is pressure-treated material or impervious moisture barrier installed wherever concrete is poured against wood construction ?


Photo Comment

13. Have plans for lateral restraint or alternate braced panels been checked, and does the construction meet the approved engineering or prescriptive design?


Photo Comment

14. Has it been confirmed that roof eave rafter tails/sheathing do not project into the fire separation distance at the property line ?


Photo Comment

15. For the braced wall panel method Portal Frame with Hold-downs (PFH), has the framing, hold-downs, and nail pattern been verified to match IRC ?


Photo Comment
Exterior Roof Sheathing

1. Is the roof sheathing inspection completed before papering or roofing?


Photo Comment

2. Are mid-span clips installed as required by the approved plan or the APA manufacturing and installation requirements ?


Photo Comment

3. Are fasteners at the end joints spaced no greater than 6 inches on center and firmly driven into the framing members, with end joints staggered ?


Photo Comment

4. Are there specified blocking and/or nailing noted in the plans?


Photo Comment

5. Where diaphragms are designated as blocked, are all joints in sheathing occurring over and fastened to common framing members or common blocking? Is the size and spacing of fasteners at wood-frame diaphragm boundaries and panel edges as prescribed by the approved plans? Are panels, not less than 4 feet by 8 feet except at boundaries and changes in framing where the minimum panel dimension is 24 inches unless all edges of the undersized panels are supported by and fastened to framing members or blocking? Are nails located at least 3/8 inch from the edges of panels?


Photo Comment

6. Are blocking, framing members, etc. nailed to the sheathing at interior shear wall locations that result in a system that provides a complete load path that meets the requirements for the transfer of loads from their point of origin through the load-resisting elements to the foundation?


Photo Comment

7. Are trusses braced to prevent rotation and provide lateral stability per the approved drawings and individual truss design drawings? In the absence of specific bracing requirements, are trusses braced in accordance with accepted industry practices such as the SBCA Building Component Safety Information (BCSI) Guide to Good Practice for Handling, Installing & Bracing of Metal Plate Connected Wood Trusses as most manufacturers require sheathing to be nailed to the blocking between trusses?


Photo Comment

8. Are plans and schedules checked for fastener type and size?


Photo Comment

9. Is the thickness and grade of sheathing conforming to approved plans or prescriptive requirements ?


Photo Comment

10. Do allowable spans for lumber sheathing conform to IRC Table?


Photo Comment

11. Is spaced lumber sheathing for wood shingle and shake roofing conforming to the requirements of sections ?


Photo Comment

12. Is spaced lumber sheathing not allowed in Seismic Design Category D2 ?


Photo Comment

Is this sample what you are looking for?
Sign up to use & customise this template, or create your own custom checklist:

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.

Easy inspection app for your digital checklists