- Library
- Property Inspection
- Mechanical Rough-In Inspection Checklist
Mechanical Rough-In Inspection Checklist
119 questions in 18 sectionsInteractive preview: try the answers
Section 1 of 18 · 4 questionsPermits And Plans
Is the job address posted in a visible location?
Are the permit and approved plans available on the site ?
Is the permit information correct, including the address, permit number, description of work, etc.?
Is the duct rough-in test affidavit on-site and available to the inspector? Is a maximum of 4 cubic feet per minute (CFM) per 100 square feet (SF) with an air handler installed or 3 CFM per 100 SF without an air handler installed?
Section 2 of 18 · 9 questionsForced-Air Furnace
Are fuel-burning appliances installed in compliance with location restrictions, such as not being in sleeping rooms, bathrooms, toilet rooms, storage closets, or spaces that open into such areas, unless they are direct vents or listed for use within living space ?
Are heat-producing equipment installations maintained with clearances to combustibles as required by the appliance listing and the manufacturer's installation instructions ?
Is the furnace room passageway a minimum of 24 inches wide ?
Are specific requirements for the installation of mechanical equipment in attics and crawl spaces followed according ?
Is the working space for mechanical equipment 30 inches deep to the height of the unit or a minimum of 30 inches (M1305.1)? Is a clearance of 3 inches provided along the sides, back, and top with a total width of the space being at least 12 inches wider than the furnace? Do furnaces having a firebox open to the atmosphere have at least a 6-inch working space along the front combustion chamber side?
Is an electrical receptacle provided at or near the appliance, within 25 feet per NEC ?
Are means of disconnect provided within sight of the appliance or is the breaker capable of being locked in the open position )?
Are switch-controlled lighting (light protected or away from access) and a receptacle outlet provided at the required passageway for servicing equipment?
Is the installation of wall furnaces performed in accordance with the listing and manufacturer's installation instructions?
Section 3 of 18 · 3 questionsUnderfloor And Antics
When a furnace is installed in an underfloor area, is it suspended a minimum of 6 inches above grade or installed on a slab extending above adjoining grade?
For equipment installed on wood platforms within 18 inches of soil to the bottom of the framing, is the framing and sheathing preservative-treated ?
Are excavations or pits for equipment installed with minimum requirements, as specified in the installation instructions ?
Section 4 of 18 · 3 questionsGarage
Are specific requirements for equipment located in garages followed, such as elevating equipment with a flame, spark, or glowing ignition source at least 18 inches above the floor, unless it's a flammable vapor ignition-resistant appliance ?
Do ducts penetrating a wall or ceiling separating the garage from the dwelling have 26-gauge construction and no openings to the garage ?
Is a bollard or wheel stop required in front of or to the side of equipment if it's subject to impact by an automobile?
Section 5 of 18 · 5 questionsCondensing Furnace (High Efficiency)
Is a condensate drain available to drain by gravity to an approved place of disposal or is a UL 508-approved condensate pump installed ?
Is the drainpipe minimum of 3/4 inch with a ? inch per foot slope ?
Is the drainpipe allowed to drain to an indirect receptor (lavatory tailpiece, tub overflow, etc.) ?
Are the piping materials correctly identified, such as the manufacturer's identification on all fittings ?
Are evaporative cooling equipment connected to potable water equipped with a backflow assembly ?
Section 6 of 18 · 13 questionsCombustion Air
Is the minimum cross-section dimension for combustion air ducting 3 inches?
Is it ensured that ducts do not displace exterior insulation of walls, floors, or ceilings and that building cavities are not used as ducts?
Is it ensured that venting systems do not extend into or pass through any fabricated air duct or furnace plenum?
Is combustion air ducting screened when terminating in an attic space ?
Is there sufficient venting when combustion air is obtained from the attic or crawl space ?
In buildings of unusually tight construction, is combustion air obtained from outside the building ?
Are indoor combustion air openings provided at a rate of 1 square inch per 1,000 Btu/h input of all appliances, but not less than a minimum of 100 square inches with at least one opening at the top and one at the bottom ?
Do outdoor combustion air openings in the attic and crawl spaces communicate directly or freely with the outdoors ?
For vertical ducts used to provide combustion air from the outdoors, is each opening sized at 1 square inch per 4,000 Btu/h of the total input rating of all appliances in the space (– Two Opening Method)?
For horizontal ducts, are the openings sized at 1 square inch per 2,000 Btu/h of the total input rating of all appliances in the space?
Is the one opening method used for combustion air, and are the openings sized at 1 square inch per 3,000 Btu/h of the total input rating of all appliances in the space, with placement within the top 12 inches of the space? The openings shall communicate directly or freely with the outdoors. ?
Are outside combustion air openings screened with corrosion-resistant mesh material not smaller than 1/4 inch ?
Is combustion air drawn from inside the building when it's of ordinary tightness, and the conditioned space is at least 50 cubic feet per 1,000 Btu/h input for all fuel-burning appliances combined ?
Section 7 of 18 · 8 questionsGeneral
Does duct-to-ground have a minimum 4-inch clearance?
Is the duct in or under concrete encased by concrete a minimum of 2 inches thick?
Do round ducts have crimped joints lapped a minimum of 1 inch and fastened with (3) sheet-metal screws or rivets equally spaced around the joint?
Are joints, seams, and fittings of ducts sealed with mastic or other approved means?
Is flexible duct supported according to the manufacturer's specifications?
Are metal ducts supported every 10 feet minimum ?
Is ductwork not displacing the required insulation of walls, floors, or ceilings, and are building cavities not used as ducts?
Is the venting system not extending into or passing through any fabricated air duct or furnace plenum?
Section 8 of 18 · 2 questionsInsulation
Are ducts, boots, and connectors used for heating or cooling insulated to at least R-8 in unconditioned spaces ?
Is it ensured that ducts do not displace exterior insulation of walls, floors, or ceilings and that building cavities are not used as ducts? Local exhaust fan ducts shall be insulated to R-4 minimum to control condensation.
Section 9 of 18 · 6 questionsReturn Air
Is return air taken from a room or space not greater than the flow rate of supply air delivered to a room or space? (M1602.2, Item 2)?
Is return air ensured that it is not taken from a closet, bathroom, toilet room, kitchen, garage, boiler room, furnace room, unconditioned attic, or other dwelling unit? Are dedicated systems serving only a garage have obtained return from the garage served? Does return air not discharge from one dwelling unit to another dwelling unit?
Are return air inlets ensured they are not located within 10 feet of any fuel-burning appliance firebox or draft hood located in the same space?
Is minimum return, air transfer openings, and duct size in accordance with appliance or equipment manufacturers’ installation instructions; Manual ”D”; or by a Registered Design Professional? (Forced air furnaces minimum outside, return air, openings 2 square inches/ kBtu/ hr. (Electric Heat pumps per UL 1995)).
Do Ducts not displace exterior insulation of walls, floors, or ceilings and is it ensured that building cavities are not used as ducts?
Do venting systems not extend into or pass through any fabricated air duct or furnace plenum?
Section 10 of 18 · 14 questionsVents And Connectors
Is the venting system installed following the manufacturer’s instructions ?
When venting two gas appliances through a common vent connector, is it ensured that the common vent connector's size is equal to the largest connector plus 50% of the smaller flue outlet and not less than the combined area of the flue outlets for which it acts as a common connector ?
Are vent connector clearances to combustibles in compliance with the manufacturer’s listing or performance standards ?
Is it verified that single-wall vents do not penetrate a wall, floor, or ceiling without a listed pass-through assembly, except for gas vents, which are allowed for exterior combustible walls only with a “ventilated metal thimble” ?
Are vent terminations installed following the manufacturer’s listing ?
For exhaust vent terminations for mechanical draft and direct venting, is the termination not less than 4 feet below or 4 feet horizontally from, and not less than 1 foot above a door, an operable window, or a gravity air inlet into a building, and not less than 3 feet above any forced air intake within 10 feet or within 12 inches of grade ?
Are specifications for gas vent terminations for listed caps for roof or wall size and clearances—see Table G2427.6.4 less than 12 inches, and not less than 8 feet from vertical wall or obstruction terminates above roof per table (pitch of roof)? Are gas vents more than 12 inches terminate 2 feet above, and 10 feet away from any portion of a building?
Is it ensured that vent terminals (except for direct vent) are not mounted directly above or within 3 feet horizontally of a gas meter or oil tank vent ?
Are vent terminals positioned no closer than 3 feet to an interior corner formed by two perpendicular walls ?
For power exhaust terminals, are they not located within 10 feet of property lines and adjacent buildings and at least 7 feet above any finished ground-level public walkway ?
Is it verified that venting systems do not extend into or pass through any fabricated air duct or furnace plenum ?
Are chimneys or vent connectors not passing through floors, walls, ceilings, or partitions unless the connector is listed and labeled for wall pass-through and installed per the listing (M1803.3.1; G2427.7.6)?
Where vents extend into an attic and pass through insulated assemblies, is an insulation shield of 26 gage sleeve not less than 2 inches above the insulation, to provide clearance between the vent and combustible insulation materials ?
Is venting supported following the manufacturer’s listing ?
Section 11 of 18 · 8 questionsAir Conditioning
Are cooling coils installed downstream (on the return side) from the heat exchanger ?
Does the working space for air conditioning equipment meet the minimum requirement of 30 inches by 30 inches ?
Is the condensate disposal line directed to an approved place of disposal, avoiding public streets, and alleys, or creating a nuisance ?
Are auxiliary and secondary drain systems (including pan) in addition to condensate disposal, where damage to any building components occurs from overflow or stoppage of condensate drain piping (four methods, including UL 508 shutoff switch)?
Is the condensate line for the air conditioning system at least 3/4 inch in diameter and sloped to drain termination without sags; 1/8 unit in 12 units (1-percent slope?
Do the refrigerants use conform to ANSI/ASHRAE 34 standards ?
Are refrigerant lines insulated to a minimum of R-4, with a maximum perm rating of 0.05 ?
Are the refrigerant circuit access ports fitted with tamper-resistant caps ?
Section 12 of 18 · 13 questionsClothes Dryer
Is the clothes dryer exhausted following the manufacturer’s instructions )?
Are the clothes dryer exhaust ducts made of metal with smooth interior surfaces, and do the joints run in the direction of airflow ?
Has a protective shield of steel plates been installed in areas where nails or screws may penetrate the clothes dryer exhaust duct, including at framing members less than 1-1/4 inches between the duct and finished face of the framing member and extend not less than 2 inches above the sole plate and beyond the top plate?
Are screws used as fasteners for the clothes dryer exhaust duct, and do they not protrude more than 1/8 inch?
Is the duct connector for the clothes dryer a minimum of 4 inches or is the appliance outlet size?
For determining dryer duct length, does the exhaust duct not exceed 35 feet, with deductions of 2-1/2 feet for each 45-degree elbow and 5 feet for each 90-degree bend for elbows, or is it determined based on the manufacturer’s installation instructions when the make and model of the dryer are provided to the Code Official at rough-in ?
Does the clothes dryer ducting run independently of other ducted systems, and does it convey moisture to the outdoors (except for listed and labeled condensing ductless clothes dryers) ?
Does the exterior termination for the clothes dryer exhaust duct have a backdraft damper with no screens, and is it at least 3 feet away from any openings into the building, and does it not connect to vent connectors, vents, or chimneys ?
If the clothes dryer ducting is concealed in construction exceeding 35 feet, has it been labeled with the equivalent length, located within 6 feet of the exhaust connection ?
Is the dryer exhaust duct installed at the time of occupancy, or if the dryer is not installed, has the exhaust duct been capped at the location of the future dryer (except for listed and labeled condensing ductless clothes dryers) ?
Is the dryer transition duct a single length, listed and labeled to UL 2158A, and a maximum of 8 feet long, and is it not concealed within construction ?
If it's a gas dryer, is the gas connector a maximum of 6 feet long, measured along the centerline of the connector; and has one connector only?
Is the gas shutoff valve installed immediately ahead of the connector?
Section 13 of 18 · 11 questionsEnergy Code Requirements
Have the approved plans specified the types of heating and cooling equipment and their associated efficiency requirements, as well as any energy credits required?
Is the duct rough-in test affidavit available on-site for inspection? Does it confirm that the maximum duct leakage is 4 CFM per 100 square feet with an air handler installed or 3 CFM per 100 square feet without the air handler ?
Have building framing cavities been avoided for use as ducts or plenums? Are ducts installed in exterior walls, floors, and ceilings without displacing required envelope insulation ?
For ducts located in conditioned spaces, are they either completely within the continuous air barrier and building thermal envelope, or do all heating, cooling, and ventilation system components be installed inside the conditioned space including, but not limited to, forced air ducts, hydronic piping, hydronic loops, convectors and radiators where combustion equipment is direct vent or sealed combustion?
For forced air ducts, is a maximum of 10 linear feet of return ducts and 5 linear feet of supply ducts permitted to be located outside the conditioned space, provided they are insulated to a minimum of R-8?
Are ducts outside the building thermal envelope insulated to a minimum of R-8, and ducts within a concrete slab or in the ground insulated to R-10 with insulation designed for below-grade use?
Have HVAC supply and return register boots been properly sealed to the subfloor, wall covering, or ceiling that they penetrate, following the guidelines in WSEC Table ?
For all detached one- and two-family dwellings and multiple single-family dwellings (townhouses) up to three stories in height above the grade plane, have inverter-driven ductless mini-split heat pumps been installed in the largest zone as the primary source of electric zonal heating, as required by?
In cases where there is a heated slab on the grade floor, has the entire area been thermally isolated from the soil with a minimum of R-10 insulation, as specified in WSEC ?
For the project, have additional energy efficiency requirements (energy credits) been met according to the following criteria, • Small Dwelling Unit: 3.0 credits - for dwelling units less than 1500 square feet in conditioned floor area with less than 300 square feet of fenestration area, or for additions to existing buildings greater than 500 square feet of heated floor area but less than 1500 square feet. • Medium Dwelling Unit: 6.0 credits - for all dwelling units that do not fall under Options 1, 3, or 4. • Large Dwelling Unit: 7.0 credits. • Dwelling units serving R-2 occupancies: 4.5 credits. • Additions less than or equal to 500 square feet: 1.5 credits .
Have the drawings included with the building permit application identified which options have been selected and the point value of each option, regardless of whether separate mechanical, plumbing, electrical, or other permits are utilized for the project?
Section 14 of 18 · 3 questionsExhaust Venting
Are source-specific ventilation fans installed in accordance with Table as amended by Washington State, in kitchens, bathrooms, and water closet rooms?
Checklist by GoAudits. This checklist is an example: we do not guarantee compliance with the laws applicable to your territory or industry. Seek professional advice to adapt it to your workplace or jurisdiction.
Free PDF
Download the Mechanical Rough-In Inspection Checklist
By downloading this checklist you agree to the GoAudits privacy policy and terms of service.
NEW! Try generating a custom checklist with our free AI tool:
Easy inspection app for your digital checklists
- Conduct inspections anytime, anywhere - even offline
- Capture photos as proof of compliance or areas needing attention
- Instantly generate and share detailed reports after the inspections
- Assign & track follow-up tasks, view historical trends on a centralized dashboard