Fire Alarm System Testing And Commissioning Checklist

Use this Fire Alarm Testing and Commissioning Checklist to verify installation, function, and documentation of all elements before final sign-off.

Fire Alarm System Testing And Commissioning Checklist



Pre-commissioning Documentation

1. Approved design drawings and specifications are on site and match the installed system.


Photo Comment

2. Fire alarm installation certification and record of completion are received from the installer.


Photo Comment

3. All equipment delivery records and manufacturer data sheets are available on site.


Photo Comment

4. The commissioning program and functional test plan have been reviewed and agreed by all parties.


Photo Comment

5. Outstanding defects or snagging items from installation are recorded and tracked.


Photo Comment
Fire Alarm Control Panel (FACP)

1. The FACP is installed in the location specified on the approved drawings.


Photo Comment

2. The panel is accessible and unobstructed for operation and maintenance.


Photo Comment

3. The panel is connected to a dedicated power circuit with correct labeling.


Photo Comment

4. Zone/address map and legend are displayed at the panel and at all remote annunciators.


Photo Comment

5. All zones and addresses are correctly identified and labeled on the panel.


Photo Comment

6. Panel indicators (power, fault, alarm) are operational and clearly visible.


Photo Comment

7. Battery backup is installed and connected correctly.


Photo Comment

8. Battery capacity meets the required standby duration per applicable standards.


Photo Comment

9. Battery charger output voltage and load voltage are within the manufacturer's specified range.


Photo Comment

10. Ground-fault monitoring circuit is functional, where provided.


Photo Comment

11. Panel clock is set to the correct date and time.


Photo Comment

12. Cause-and-effect programming matches the approved design matrix.


Photo Comment
Detection Devices

1. All smoke detectors are installed at the locations specified on the approved drawings.


Photo Comment

2. All heat detectors are installed at the locations specified on the approved drawings.


Photo Comment

3. Manual call points (pull stations) are installed at the correct height and travel distance per applicable standards.


Photo Comment

4. Duct smoke detectors are installed in the correct positions relative to air-handling units.


Photo Comment

5. Beam detectors are aligned and set per manufacturer instructions, where installed.


Photo Comment

6. All detectors are free from physical damage, obstructions, and contamination.


Photo Comment

7. Each detector address or zone corresponds correctly with the panel display.


Photo Comment

8. A sample of smoke and heat detectors (minimum 10%) has been function-tested using appropriate test equipment.


Photo Comment

9. Each manual call point has been activated and confirmed at the panel.


Photo Comment

10. Duct detectors have been tested to confirm fan shutdown and panel alarm signal.


Photo Comment

11. Air sampling and flame detectors have been tested per manufacturer instructions, where installed.


Photo Comment
Notification Appliances

1. Sounders and alarm devices are installed at the locations specified on the approved drawings.


Photo Comment

2. Alarm audibility has been measured and exceeds the required level above ambient noise throughout the building.


Photo Comment

3. Alarm tone pattern (e.g., temporal three-pulse) matches the specified design.


Photo Comment

4. Strobe devices are mounted at the correct height and candela rating per applicable standards.


Photo Comment

5. In areas with multiple strobe devices, flash synchronization has been verified.


Photo Comment

6. Voice evacuation messages are clear, distinct, and audible in all areas, where provided.


Photo Comment

7. Emergency voice/alarm communication phone jacks are operational, where provided.


Photo Comment

8. Alarm devices activate correctly on operation of the sprinkler flow switch.


Photo Comment
Wiring And Cable

1. Cable type and gauge match the approved drawings throughout the installation.


Photo Comment

2. Device locations and wiring routes match the approved drawings.


Photo Comment

3. All cables are correctly terminated and labeled at both ends.


Photo Comment

4. Loop resistance for all circuits is within the manufacturer's and design specifications.


Photo Comment

5. All wiring is segregated from other services in accordance with applicable standards.


Photo Comment

6. No visible damage to cables, conduits, or trunking is present.


Photo Comment

7. End-of-line devices are correctly installed on all supervised circuits.


Photo Comment

8. A trouble condition has been induced on each circuit and confirmed at the panel.


Photo Comment
System Integration And Cause & Effect

1. HVAC systems shut down correctly on activation of the relevant detection zones.


Photo Comment

2. Magnetic door-hold-open devices release correctly on alarm activation.


Photo Comment

3. Elevator(s) return to the designated floor and alternate floor on alarm, where applicable.


Photo Comment

4. Sprinkler tamper switches generate a supervisory (not alarm) signal at the panel.


Photo Comment

5. Sprinkler flow switches generate a full alarm signal at the panel.


Photo Comment

6. Kitchen hood suppression system, clean agent systems, and other suppression interfaces activate the fire alarm correctly, where applicable.


Photo Comment

7. Monitoring station (alarm receiving centre) has confirmed receipt of alarm, trouble, and supervisory signals as distinct signals.


Photo Comment

8. Correct signal type is confirmed at the monitoring station for each test condition.


Photo Comment

9. System response time from detector activation to notification does not exceed 10 seconds.


Photo Comment
Power Supply And Secondary Power Testing

1. System switches to secondary (battery) power correctly when primary supply is interrupted.


Photo Comment

2. Power indicator and trouble signal operate correctly on secondary power.


Photo Comment

3. Standby current demand and alarm current demand on secondary power are within design limits.


Photo Comment

4. Supervisory signals (fire pumps, water level/temperature, pressure switches, control valves) operate correctly on secondary power, where applicable.


Photo Comment

5. Silence switch operates correctly; a second initiating zone overrides the silence function.


Photo Comment

6. Trouble and alarm reset switches operate correctly.


Photo Comment

7. Panel lamp test switch operates correctly, where provided.


Photo Comment
Documentation And Handover

1. As-built drawings reflect any variations from the approved design and are signed off.


Photo Comment

2. All test results, including device addresses and pass/fail outcomes, are recorded in the commissioning report.


Photo Comment

3. Operating and maintenance manuals are complete and handed over to the building owner or facilities manager.


Photo Comment

4. The system owner or facilities manager has been given a demonstration of panel operation and reset procedures.


Photo Comment

5. Commissioning certificate is completed and signed by the commissioning engineer.


Photo Comment

6. Outstanding items or deferred tests are listed with agreed completion dates.


Photo Comment