Electrical Distribution Board Inspection Checklist

Use this Electrical Distribution Board Inspection Checklist to audit DB enclosures, MCBs, RCDs, earthing, busbars, and circuit labeling for compliance.

Electrical Distribution Board Inspection Checklist



Documentation And Pre-inspection Checks

1. The circuit schedule or distribution board chart is available on site for reference during the inspection


Photo Comment

2. Records from the previous DB inspection are available and have been reviewed


Photo Comment

3. Any defects identified during the previous inspection have been actioned and closed out


Photo Comment

4. All test equipment to be used during the inspection is within its current calibration period


Photo Comment

5. A valid permit to work or isolation certificate is in place where required before any de-energized testing


Photo Comment

6. The inspector has confirmed appropriate PPE is available and in use, including insulated gloves and safety glasses


Photo Comment

7. The DB location and reference number are recorded for this inspection report


Photo Comment
Enclosure And Physical Condition

1. The distribution board enclosure is free of physical damage, dents, cracks, or corrosion


Photo Comment

2. The DB is securely mounted to the wall or structure with no movement when tested


Photo Comment

3. The area in front of the DB provides adequate clear working space for safe access


Photo Comment

4. The DB is not located in an area that exposes it to excessive moisture, heat, or mechanical damage without appropriate IP-rated protection


Photo Comment

5. The enclosure door opens and closes fully and the locking mechanism operates correctly


Photo Comment

6. All unused cable entry knockouts are blanked off with appropriate fittings — no open apertures are present


Photo Comment

7. Ventilation slots or grilles on the enclosure are clear and unobstructed


Photo Comment

8. A hazard warning label is present and legible on the DB enclosure


Photo Comment

9. No combustible materials are stored adjacent to or in contact with the distribution board


Photo Comment
Busbars And Internal Components

1. The busbar assembly is free of signs of overheating, discoloration, arcing, or physical damage


Photo Comment

2. Phase barriers between busbars are present, intact, and correctly positioned


Photo Comment

3. All busbar connections are tight with no visible signs of looseness or corrosion


Photo Comment

4. No unauthorized modifications or improvised connections are present within the DB


Photo Comment

5. Insulating sleeves or shrouding on live busbars are in good condition with no cracks or missing sections


Photo Comment

6. The DB interior is clean and free of debris, dust buildup, or moisture ingress


Photo Comment
Circuit Breakers And Protective Devices

1. All MCBs and MCCBs are correctly rated for the circuits they protect and match the circuit schedule


Photo Comment

2. No MCB or MCCB shows signs of physical damage, heat discoloration, or burning at the terminals


Photo Comment

3. Each MCB and MCCB operates correctly — the handle moves freely between on, off, and tripped positions


Photo Comment

4. Each MCB and MCCB can be manually tripped and reset without mechanical resistance or failure


Photo Comment

5. No circuit breakers have been bridged, bypassed, or otherwise defeated


Photo Comment

6. Where fuse carriers or fuse bases are fitted, fuses are of the correct type and rating for each circuit


Photo Comment

7. All spare ways within the DB are fitted with blanking plates or isolating covers


Photo Comment
RCD And RCBO Testing

1. All RCDs and RCBOs are present as required by the circuit schedule and applicable wiring regulations


Photo Comment

2. Each RCD and RCBO is correctly rated for its circuit — confirm type (Type AC, Type A, or Type B) and sensitivity (mA rating)


Photo Comment

3. Each RCD is tested using the integral test button and trips correctly on operation


Photo Comment

4. Each RCBO is tested using the integral test button and trips correctly on operation


Photo Comment

5. All RCDs and RCBOs reset successfully following the test button operation


Photo Comment

6. Where portable RCD test equipment is available, trip times are measured and recorded against acceptable limits


Photo Comment

7. The date of the last periodic RCD test is recorded on the DB or in the inspection records


Photo Comment
Earthing And Bonding

1. The earth busbar or terminal block is present, correctly connected, and free of corrosion


Photo Comment

2. All protective conductors (CPCs) terminating at the earth busbar are securely connected and correctly identified


Photo Comment

3. The main earthing conductor connection to the earth busbar is tight and in good condition


Photo Comment

4. Main equipotential bonding conductors for incoming services (gas, water, structural steel where applicable) are connected and in good condition


Photo Comment

5. Where a supplementary bonding conductor is required, it is present and correctly terminated


Photo Comment

6. No earth conductor terminals show signs of corrosion, discoloration, or loose connections


Photo Comment

7. The earth busbar is correctly bonded to the DB enclosure


Photo Comment
Cable Entries And Terminations

1. All cables enter the DB through correct cable glands or conduit fittings that provide mechanical support and IP protection at the entry point


Photo Comment

2. Cable glands and conduit entries are tight with no cables subject to mechanical strain at the entry point


Photo Comment

3. All cable insulation is in good condition at entry points with no cracking, abrasion, or damage to the outer sheath


Photo Comment

4. Core identification (colour coding or ferrule marking) is correct and consistent throughout the DB


Photo Comment

5. All conductor terminations at MCB, MCCB, RCD, RCBO, and busbar connections are tight with no exposed live conductors beyond the terminal


Photo Comment

6. No cables are routed in a way that places them in contact with sharp edges, hot surfaces, or moving parts inside the enclosure


Photo Comment

7. Cable and conductor sizes are appropriate for the protective device rating of each circuit


Photo Comment
Circuit Schedule And Labeling

1. A legible, up-to-date circuit schedule is fitted inside the DB door or adjacent to the board


Photo Comment

2. The circuit schedule accurately reflects the current circuit configuration — no unlabeled or incorrectly labeled ways


Photo Comment

3. Each MCB, MCCB, RCD, and RCBO way is individually labeled with the circuit it serves


Photo Comment

4. Phase identification is clearly marked on all three-phase circuits within the DB


Photo Comment

5. The DB reference number or designation label is present and matches the building's electrical documentation


Photo Comment

6. The DB incoming supply voltage and maximum demand rating are recorded on the schedule or enclosure label


Photo Comment
Thermal And Operational Checks

1. No unusual heat is detectable at the DB enclosure surface during normal operation


Photo Comment

2. No smell of burning, hot insulation, or overheated plastic is detected in the vicinity of the DB


Photo Comment

3. No audible abnormalities such as buzzing, crackling, or humming are present during energized operation


Photo Comment

4. No visible signs of smoke staining, soot, or heat damage are present on the enclosure interior or exterior


Photo Comment

5. Measured ambient temperature in the DB room or enclosure is within acceptable operating limits for the installed equipment


Photo Comment

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.

Is this sample what you are looking for?
Sign up to use & customize this template, or create your own custom checklist.

NEW! Try generating a custom checklist with our free AI tool:

Easy inspection app for your digital checklists