Electrical Distribution Board Inspection Checklist

Use this Electrical Distribution Board Inspection Checklist to audit DB enclosures, MCBs, RCDs, earthing, busbars, and circuit labeling for compliance.

Electrical Distribution Board Inspection Checklist



61 questions in 9 sectionsInteractive preview: try the answers

Section 1 of 9 · 7 questions

Documentation And Pre-inspection Checks

  1. The circuit schedule or distribution board chart is available on site for reference during the inspection

  2. Records from the previous DB inspection are available and have been reviewed

  3. Any defects identified during the previous inspection have been actioned and closed out

  4. All test equipment to be used during the inspection is within its current calibration period

  5. A valid permit to work or isolation certificate is in place where required before any de-energized testing

  6. The inspector has confirmed appropriate PPE is available and in use, including insulated gloves and safety glasses

  7. The DB location and reference number are recorded for this inspection report

Section 2 of 9 · 9 questions

Enclosure And Physical Condition

  1. The distribution board enclosure is free of physical damage, dents, cracks, or corrosion

  2. The DB is securely mounted to the wall or structure with no movement when tested

  3. The area in front of the DB provides adequate clear working space for safe access

  4. The DB is not located in an area that exposes it to excessive moisture, heat, or mechanical damage without appropriate IP-rated protection

  5. The enclosure door opens and closes fully and the locking mechanism operates correctly

  6. All unused cable entry knockouts are blanked off with appropriate fittings — no open apertures are present

  7. Ventilation slots or grilles on the enclosure are clear and unobstructed

  8. A hazard warning label is present and legible on the DB enclosure

  9. No combustible materials are stored adjacent to or in contact with the distribution board

Section 3 of 9 · 6 questions

Busbars And Internal Components

  1. The busbar assembly is free of signs of overheating, discoloration, arcing, or physical damage

  2. Phase barriers between busbars are present, intact, and correctly positioned

  3. All busbar connections are tight with no visible signs of looseness or corrosion

  4. No unauthorized modifications or improvised connections are present within the DB

  5. Insulating sleeves or shrouding on live busbars are in good condition with no cracks or missing sections

  6. The DB interior is clean and free of debris, dust buildup, or moisture ingress

Section 4 of 9 · 7 questions

Circuit Breakers And Protective Devices

  1. All MCBs and MCCBs are correctly rated for the circuits they protect and match the circuit schedule

  2. No MCB or MCCB shows signs of physical damage, heat discoloration, or burning at the terminals

  3. Each MCB and MCCB operates correctly — the handle moves freely between on, off, and tripped positions

  4. Each MCB and MCCB can be manually tripped and reset without mechanical resistance or failure

  5. No circuit breakers have been bridged, bypassed, or otherwise defeated

  6. Where fuse carriers or fuse bases are fitted, fuses are of the correct type and rating for each circuit

  7. All spare ways within the DB are fitted with blanking plates or isolating covers

Section 5 of 9 · 7 questions

RCD And RCBO Testing

  1. All RCDs and RCBOs are present as required by the circuit schedule and applicable wiring regulations

  2. Each RCD and RCBO is correctly rated for its circuit — confirm type (Type AC, Type A, or Type B) and sensitivity (mA rating)

  3. Each RCD is tested using the integral test button and trips correctly on operation

  4. Each RCBO is tested using the integral test button and trips correctly on operation

  5. All RCDs and RCBOs reset successfully following the test button operation

  6. Where portable RCD test equipment is available, trip times are measured and recorded against acceptable limits

  7. The date of the last periodic RCD test is recorded on the DB or in the inspection records

Section 6 of 9 · 7 questions

Earthing And Bonding

  1. The earth busbar or terminal block is present, correctly connected, and free of corrosion

  2. All protective conductors (CPCs) terminating at the earth busbar are securely connected and correctly identified

  3. The main earthing conductor connection to the earth busbar is tight and in good condition

  4. Main equipotential bonding conductors for incoming services (gas, water, structural steel where applicable) are connected and in good condition

  5. Where a supplementary bonding conductor is required, it is present and correctly terminated

  6. No earth conductor terminals show signs of corrosion, discoloration, or loose connections

  7. The earth busbar is correctly bonded to the DB enclosure

Section 7 of 9 · 7 questions

Cable Entries And Terminations

  1. All cables enter the DB through correct cable glands or conduit fittings that provide mechanical support and IP protection at the entry point

  2. Cable glands and conduit entries are tight with no cables subject to mechanical strain at the entry point

  3. All cable insulation is in good condition at entry points with no cracking, abrasion, or damage to the outer sheath

  4. Core identification (colour coding or ferrule marking) is correct and consistent throughout the DB

  5. All conductor terminations at MCB, MCCB, RCD, RCBO, and busbar connections are tight with no exposed live conductors beyond the terminal

  6. No cables are routed in a way that places them in contact with sharp edges, hot surfaces, or moving parts inside the enclosure

  7. Cable and conductor sizes are appropriate for the protective device rating of each circuit

Section 8 of 9 · 6 questions

Circuit Schedule And Labeling

  1. A legible, up-to-date circuit schedule is fitted inside the DB door or adjacent to the board

  2. The circuit schedule accurately reflects the current circuit configuration — no unlabeled or incorrectly labeled ways

  3. Each MCB, MCCB, RCD, and RCBO way is individually labeled with the circuit it serves

  4. Phase identification is clearly marked on all three-phase circuits within the DB

  5. The DB reference number or designation label is present and matches the building's electrical documentation

  6. The DB incoming supply voltage and maximum demand rating are recorded on the schedule or enclosure label

Section 9 of 9 · 5 questions

Thermal And Operational Checks

  1. No unusual heat is detectable at the DB enclosure surface during normal operation

  2. No smell of burning, hot insulation, or overheated plastic is detected in the vicinity of the DB

  3. No audible abnormalities such as buzzing, crackling, or humming are present during energized operation

  4. No visible signs of smoke staining, soot, or heat damage are present on the enclosure interior or exterior

  5. Measured ambient temperature in the DB room or enclosure is within acceptable operating limits for the installed equipment

Checklist by GoAudits. This checklist is an example: we do not guarantee compliance with the laws applicable to your territory or industry. Seek professional advice to adapt it to your workplace or jurisdiction.

Free PDF

Download the Electrical Distribution Board Inspection Checklist

By downloading this checklist you agree to the GoAudits privacy policy and terms of service.

NEW! Try generating a custom checklist with our free AI tool:

Easy inspection app for your digital checklists