Air Handling Unit Checklist

Use this Air Handling Unit Checklist to ensure optimal performance and energy efficiency of air handling units, covering key components like filters, fans, controls, and more.

Air Handling Unit Checklist



Verify Proper Operation Of Air Dampers

1. Are all AHU dampers operating correctly?


Photo Comment

2. Has an operator sent a control signal to open and close all dampers and visually confirmed full operation?


Photo Comment

3. Are the dampers able to modulate to approximately 50% open position correctly?


Photo Comment

4. Are any actuators or damper banks in need of repair?


Photo Comment

5. Do the existing dampers require modulating actuators to allow for variable outside airflow?


Photo Comment
Verify Proper Operation Of Air-side Economizer

1. Is the current control system using an air-side economizer as per the DDC sequence?


Photo Comment

2. Is the economizer working correctly across different outside air temperatures, as verified by damper position and outside airflow rates?


Photo Comment

3. If no air-side economizer function is used, is it feasible to enable one for the system?


Photo Comment

4. Are the outside air temperature sensors functioning correctly for dry bulb economizer control?


Photo Comment

5. Is the outside air relative humidity sensor functional and in place for enthalpy-based economizer control?


Photo Comment
Verify Proper Operation Of Heating And Cooling Valves

1. Are all heating and cooling valves operating correctly?


Photo Comment

2. In winter, does the heating valve shut off properly without continuing to heat the supply air?


Photo Comment

3. Are any valves failing to seat correctly, leading to simultaneous heating and cooling?


Photo Comment

4. Are the same procedures being followed for analyzing the cooling coil?


Photo Comment
Check The Condition Of Heating And Cooling Coils And AHU Filters

1. Have the heating and cooling coils and AHU filters been visually inspected for cleanliness?


Photo Comment

2. Are dirty coils or clogged filters being replaced or cleaned as needed?


Photo Comment

3. Does the current maintenance schedule need to be revised to prevent filter and coil fouling?


Photo Comment

4. Are static pressure sensors (used for filter dirt loading) working correctly?


Photo Comment

5. Are dirty coils or filters causing increased static pressure and energy use?


Photo Comment
Eliminate Duct Leakage

1. Have the HVAC duct runs been traced and inspected for air leaks?


Photo Comment

2. Is the duct static pressure setpoint within the pressure class of the installed ductwork before repairs are made?


Photo Comment

3. If significant duct leakage is found, should the ductwork be replaced or sealed using a duct sealant system?


Photo Comment
Eliminate 100% Of Outside Air Systems If Practicable

1. Are any 100% outside air AHUs serving areas that don’t require 100% outside air?


Photo Comment

2. Can modulating outside air dampers and return air systems be installed to reduce unnecessary outside air?


Photo Comment
Reduce Outside Airflow Rates To ASHRAE 62.1-2010

1. Are current outside airflow rates above ASHRAE 62.1-2010 minimum requirements for each space?


Photo Comment

2. Should CO₂ sensors be installed in return air ducts to maintain acceptable indoor CO₂ levels?


Photo Comment

3. Can an outside air damper reset schedule be implemented based on time of day and occupancy?


Photo Comment

4. Are outside air dampers closing fully during unoccupied hours and morning warm-up?


Photo Comment
Implement An HVAC System Night Setback Schedule

1. Have night setback controls been implemented for HVAC systems in non-24/7 areas?


Photo Comment

2. Have operational hours and acceptable temperature limits of equipment in these areas been confirmed?


Photo Comment
Track HVAC Setback

1. Are HVAC system trend logs being used to verify if systems are entering night setback mode?


Photo Comment

2. If systems are running at night, can the unoccupied temperature range be adjusted to avoid unnecessary operation?


Photo Comment

3. Is anything in space causing the temperature to go out of range at night?


Photo Comment

4. Has an optimum start/stop sequence been implemented through the BAS or programmable thermostat?


Photo Comment
Monitor Exhaust Fan Controls

1. Are exhaust fans in HVAC zones with night setbacks shutting down on the same schedule as the HVAC system?


Photo Comment

2. Are exhaust fans left running 24/7, causing unwanted negative pressure and unconditioned air infiltration?


Photo Comment

3. Can exhaust fan operation be reduced at night with VFDs or scheduled shutdowns?


Photo Comment
Slow Down Systems During Unoccupied Hours

1. Is outside air intake reset to a lower level (0–5% open) during unoccupied hours?


Photo Comment

2. Is the minimum airflow reset to a lower value (e.g., 33%–50% of normal flow)?


Photo Comment

3. Is the supply air static pressure or fan speed reset to a lower level during low occupancy?


Photo Comment

Is this sample what you are looking for?
Sign up to use & customise this template, or create your own custom checklist:

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.

Easy inspection app for your digital checklists