Substation Commissioning Checklist

Use the Substation Commissioning Checklist template to verify the installation, and confirm components from transformers to motors meet safety standards.

Substation Commissioning Checklist



Direct Current (D.C.) Battery System

1. Is the condition of the battery system satisfactory?


Photo Comment

2. Has the voltage of each battery cell been measured?


Photo Comment

3. Are other inspection items required by the manufacturers of related equipment satisfactory?


Photo Comment
Operation And Testing Tools And Equipment

1. Are proper operation tools and equipment provided for switching and isolation use?


Photo Comment

2. Is a suitable self-test high voltage tester provided for verifying equipment dead?


Photo Comment

3. Are other inspection items required by the manufacturers of related equipment satisfactory?


Photo Comment
Safety Precaution

1. Are safety requirements for testing of H.V. installations recommended by manufacturers of related equipment and executed?


Photo Comment

2. Are proper precautionary measures taken, and are the methods of tests such that no danger to persons or property can occur even if the circuit being tested is defective?


Photo Comment
Testing

1. Are testing requirements and detailed test procedures for H.V. installations recommended by manufacturers of related equipment and approved?


Photo Comment

2. Are all tests for H.V. installations recorded in separate forms and properly endorsed?


Photo Comment
Lightning Protection System

1. Has the continuity between air terminations and earthing terminations been tested?


Photo Comment

2. Is the measured earth termination network resistance to earth, not more than 10 Ohms when the connection to the main earthing terminal is disconnected?


Photo Comment

3. Are test results recorded?


Photo Comment
Circuitry Check

1. Have all circuits, including lighting and power circuits, been verified through switching operation to ensure they are installed in accordance with the designated circuits?


Photo Comment
Charger And Battery Set

1. Have the original factory test certificates of the charger and battery been checked and found satisfactory?


Photo Comment

2. Is the charger connected to the main supply through a suitably rated fuse?


Photo Comment

3. Have battery connections been done properly?


Photo Comment

4. Are instruments, indicating lamps, fuses, relays, and labels on the battery charger provided and installed properly?


Photo Comment

5. Is the capacity of the charger sufficient to recharge the batteries from fully discharged to fully charged within the specified duration?


Photo Comment

6. Is the charger output on load with batteries disconnected satisfactory?


Photo Comment

7. Is the charger current on load with batteries disconnected satisfactory?


Photo Comment

8. Are proper operation tools and equipment provided for switching and isolation use?


Photo Comment

9. Is a suitable self-test high voltage tester provided for verifying equipment dead?


Photo Comment

10. Are other inspection items required by the manufacturers of related equipment satisfactory?


Photo Comment

11. Has the capacity of the batteries been checked and tested by interrupting the mains input to the charger and the actuation/operation of connected devices, with satisfactory results?


Photo Comment

12. Have the functions and indications of charger fail, main fail, battery disconnected, boost charge, trickle charge, mains, and battery been checked and tested with satisfactory results?


Photo Comment
Luminaires And Lighting Fittings

1. Was the color temperature of light fittings checked and found as specified?


Photo Comment

2. Are all lamps of the correct wattage and voltage ratings?


Photo Comment

3. Is the beam angle of spot lamps commissioned?


Photo Comment

4. Is the aiming angle of external lighting or planter lighting commissioned to avoid glare or obstruction to the external environment?


Photo Comment

5. Have exterior flood lights been aimed according to requirements (particularly relevant for sports installations)?


Photo Comment

6. Do fluorescent lamps have the correct phosphor?


Photo Comment
Lighting Control (On/Off And Dimming)

1. Are groups of luminaires assigned to the correct positions in grid switches or grid single circuit dimmers and tested by hand operation?


Photo Comment

2. Is the lighting control system (e.g., timer switch, occupancy sensor, photocell, infra-red sensor) correctly commissioned and set?


Photo Comment

3. Does the timer switch operated lighting control system properly operate as commissioned?


Photo Comment

4. Does the photocell-operated lighting control system properly operate as commissioned?


Photo Comment

5. Does the infra-red sensor-operated lighting control system properly operate as commissioned?


Photo Comment

6. Does the occupancy sensor-operated lighting control system properly operate as commissioned?


Photo Comment

7. Are FM radio switches configured to the relevant receivers?


Photo Comment

8. Is the lighting control by CCMS or BMS tested and properly functioning?


Photo Comment
Lighting Measurement

1. Is the illuminance level of the lighting installation measured for individual areas/rooms under its design conditions?


Photo Comment

2. Are measurement results recorded?


Photo Comment
Digital Multifunction Power Meter

1. Is the manufacturer’s calibration certificate for each meter provided?


Photo Comment

2. Are the readings of electrical parameters by the meter and by the test kit recorded?


Photo Comment

3. Are remote monitoring functions by CCMS or BMS tested and found satisfactory?


Photo Comment

4. Are interfacing functions for the self-contained meter tested using a plug-in communication module and found satisfactory?


Photo Comment

5. Is the replacement mechanism of the meter tested and found satisfactory?


Photo Comment

6. Is a current transformer (C.T.) shorting block provided and tested to prevent open circuiting the C.T.?


Photo Comment
Digital Power Analyzer

1. Is the manufacturer’s calibration certificate for each power analyzer provided?


Photo Comment

2. Are the readings of electrical parameters by the digital power analyzer and by the test kit recorded?


Photo Comment

3. Are remote monitoring functions by CCMS or BMS tested and found satisfactory?


Photo Comment

4. Are interfacing functions for the self-contained digital power analyzer tested using a plug-in communication module and found satisfactory?


Photo Comment

5. Is the replacement mechanism of the meter tested and found satisfactory?


Photo Comment

6. Is a current transformer (C.T.) shorting block provided and tested to prevent open circuiting the C.T.?


Photo Comment

7. Are the event alarm and waveform capture functions of the digital power analyzer tested and found satisfactory?


Photo Comment
Busbar Trunking System

1. Is a type test certificate issued by testing laboratories or organizations as stated in the COP provided?


Photo Comment

2. Have the bolts, nuts, screws, etc., for busbar supports and connections been checked for correct tightness in accordance with manufacturers' recommendations?


Photo Comment

3. Is no dust, foreign particles, or deleterious substances accumulated on the busbar trunking system, and is the system free from condensation?


Photo Comment

4. Have continuity, insulation resistance, polarity, earth fault loop impedance, and other required tests been carried out, recorded, and found satisfactory?


Photo Comment

5. Is phase transposition of the busbar trunking in the long run in accordance with the manufacturer's recommendation provided?


Photo Comment

6. Is the operation of the plug-in tap-off unit tested and found satisfactory?


Photo Comment

7. Are the mechanical interlock, quick fastening, and quick releasing mechanisms of the tap-off unit tested and found satisfactory?


Photo Comment

8. Is infrared scanning at selective connection joints carried out to check for hot temperature spots?


Photo Comment
Transformers/Motors

1. Is there no visible damage that could impair safety?


Photo Comment

2. Are all accessible live parts screened with insulating plates or earthed metal?


Photo Comment

3. Is proper ventilation provided to avoid excessive temperature rise?


Photo Comment

4. Have initial/maintenance tests been carried out according to relevant recognized standards and manufacturers' recommendations, with test reports (e.g., insulation resistance test, pressure test)?


Photo Comment

5. Are other inspection items required by the manufacturers of related equipment satisfactory?


Photo Comment
Earth

1. Is a warning notice 'Safety Electrical Connection—Do Not Remove' provided at all main earthing and bonding connections?


Photo Comment

2. Are earthing conductors of adequate size?


Photo Comment

3. Are other inspection items required by the manufacturers of related equipment satisfactory?


Photo Comment