RTU Maintenance Checklist for Rooftop Units
50 questions in 10 sectionsInteractive preview: try the answers
Section 1 of 10 · 4 questionsAsset Records And Service History
Unit make, model, and serial number
Asset or tag number and roof position of the unit being serviced
Refrigerant type and nameplate charge
Defects raised at the previous PM visit have been closed out
Section 2 of 10 · 5 questionsRoof Access And Safety
Roof access is authorized and the access hatch or ladder is secure and in good condition
Fall protection is used where work takes place within the unprotected roof edge zone
Weather conditions on the roof are safe for the planned work
The unit is switched off at the service disconnect and locked off before any panel is opened
Personal protective equipment for sharp edges, electrical work, and coil cleaning is worn
Section 3 of 10 · 5 questionsRoof Curb And Mounting
Curb flashing is intact and sealed, with no lifted edges or open laps
Sealant at the roof penetration for power and control conduit is sound
The roof membrane around the unit is free of punctures, tears, and foot traffic damage
No ponding water is present around the curb or the condensate discharge point
Tie-downs, wind restraints, and vibration isolators are secure and not perished
Section 4 of 10 · 5 questionsCabinet And Filters
All cabinet panels are refitted with fasteners complete and gaskets seating cleanly
Cabinet corrosion is limited to surface rust, with no perforation of panels or base rails
Coil guards and hail guards are undamaged and correctly positioned
Filters are replaced or cleaned and seated with no bypass gaps at the rack
Filter differential pressure is within the manufacturer's stated limit
Section 5 of 10 · 6 questionsSupply Fan, Evaporator, And Condensate
Motor and fan sheaves are aligned, with no drive wobble or shaft play
The supply fan wheel is clean and turns freely with no bearing noise
The evaporator coil is clean and free of fouling, ice, and refrigerant oil staining
The drain pan is clean, drains fully, and shows no corrosion or standing water
The condensate trap is correctly configured and primed
The condensate line is clear and discharges to the roof drain without pooling
Section 6 of 10 · 6 questionsCondenser And Refrigerant Circuit
Suction and discharge pressures and measured superheat
The condenser coil is clean across its full depth, with debris cleared from between rows
Condenser fins are straight and free of corrosion, with bent areas combed out
Condenser fan blades are clean and undamaged, and the fan guard is secure
No oil staining is present at brazed joints, service valves, or the compressor body
Refrigerant added or recovered is weighed and logged against this unit
Section 7 of 10 · 5 questionsEconomizer And Outside Air
The economizer dampers travel through their full stroke without binding or overshoot
The damper actuator and linkage are secure, with no slipped couplings or stripped gears
The changeover sensor reads correctly and free cooling enables at its setpoint
Dampers hold the specified minimum outside air position when the unit runs occupied
The outside air hood and intake screen are clear and drain without water carryover
Section 8 of 10 · 4 questionsGas Heat Section
The heat exchanger shows no cracking, separation, soot, or scale on accessible surfaces
Burners are clean and the flame pattern is stable across all burners
The flue terminal is clear, correctly oriented, and free of corrosion at the roof line
The gas connection at the unit is leak free and the manual shutoff is accessible
Section 9 of 10 · 5 questionsElectrical And Controls
The roof service disconnect is labeled, weather-tight, and operates cleanly
Contactors and relays are free of pitting, welding, and heat discoloration
Run and start capacitors measure within tolerance of their nameplate rating
High and low pressure switches and the freeze stat operate at their set values
Active fault codes on the unit controller are recorded and cleared after resolution
Section 10 of 10 · 5 questionsPerformance Verification
Return air and supply air temperatures at the unit
Compressor and fan motor amp draw on each phase
Measured amp draw is within nameplate limits for the compressor and each motor
Each cooling stage loads and unloads in sequence without short cycling
The occupied and unoccupied schedule on the controller matches actual building use
Checklist by GoAudits. This checklist is an example: we do not guarantee compliance with the laws applicable to your territory or industry. Seek professional advice to adapt it to your workplace or jurisdiction.
Free PDF
Download the RTU Maintenance Checklist for Rooftop Units
By downloading this checklist you agree to the GoAudits privacy policy and terms of service.
NEW! Try generating a custom checklist with our free AI tool:
Easy inspection app for your digital checklists
- Conduct inspections anytime, anywhere - even offline
- Capture photos as proof of compliance or areas needing attention
- Instantly generate and share detailed reports after the inspections
- Assign & track follow-up tasks, view historical trends on a centralized dashboard