RTU Maintenance Checklist for Rooftop Units

Use this RTU Maintenance Checklist for HVAC rooftop units to check the roof curb, coils, economizer, gas heat section, and controls on every PM visit.

RTU Maintenance Checklist for Rooftop Units



50 questions in 10 sectionsInteractive preview: try the answers

Section 1 of 10 · 4 questions

Asset Records And Service History

  1. Unit make, model, and serial number

  2. Asset or tag number and roof position of the unit being serviced

  3. Refrigerant type and nameplate charge

  4. Defects raised at the previous PM visit have been closed out

Section 2 of 10 · 5 questions

Roof Access And Safety

  1. Roof access is authorized and the access hatch or ladder is secure and in good condition

  2. Fall protection is used where work takes place within the unprotected roof edge zone

  3. Weather conditions on the roof are safe for the planned work

  4. The unit is switched off at the service disconnect and locked off before any panel is opened

  5. Personal protective equipment for sharp edges, electrical work, and coil cleaning is worn

Section 3 of 10 · 5 questions

Roof Curb And Mounting

  1. Curb flashing is intact and sealed, with no lifted edges or open laps

  2. Sealant at the roof penetration for power and control conduit is sound

  3. The roof membrane around the unit is free of punctures, tears, and foot traffic damage

  4. No ponding water is present around the curb or the condensate discharge point

  5. Tie-downs, wind restraints, and vibration isolators are secure and not perished

Section 4 of 10 · 5 questions

Cabinet And Filters

  1. All cabinet panels are refitted with fasteners complete and gaskets seating cleanly

  2. Cabinet corrosion is limited to surface rust, with no perforation of panels or base rails

  3. Coil guards and hail guards are undamaged and correctly positioned

  4. Filters are replaced or cleaned and seated with no bypass gaps at the rack

  5. Filter differential pressure is within the manufacturer's stated limit

Section 5 of 10 · 6 questions

Supply Fan, Evaporator, And Condensate

  1. Motor and fan sheaves are aligned, with no drive wobble or shaft play

  2. The supply fan wheel is clean and turns freely with no bearing noise

  3. The evaporator coil is clean and free of fouling, ice, and refrigerant oil staining

  4. The drain pan is clean, drains fully, and shows no corrosion or standing water

  5. The condensate trap is correctly configured and primed

  6. The condensate line is clear and discharges to the roof drain without pooling

Section 6 of 10 · 6 questions

Condenser And Refrigerant Circuit

  1. Suction and discharge pressures and measured superheat

  2. The condenser coil is clean across its full depth, with debris cleared from between rows

  3. Condenser fins are straight and free of corrosion, with bent areas combed out

  4. Condenser fan blades are clean and undamaged, and the fan guard is secure

  5. No oil staining is present at brazed joints, service valves, or the compressor body

  6. Refrigerant added or recovered is weighed and logged against this unit

Section 7 of 10 · 5 questions

Economizer And Outside Air

  1. The economizer dampers travel through their full stroke without binding or overshoot

  2. The damper actuator and linkage are secure, with no slipped couplings or stripped gears

  3. The changeover sensor reads correctly and free cooling enables at its setpoint

  4. Dampers hold the specified minimum outside air position when the unit runs occupied

  5. The outside air hood and intake screen are clear and drain without water carryover

Section 8 of 10 · 4 questions

Gas Heat Section

  1. The heat exchanger shows no cracking, separation, soot, or scale on accessible surfaces

  2. Burners are clean and the flame pattern is stable across all burners

  3. The flue terminal is clear, correctly oriented, and free of corrosion at the roof line

  4. The gas connection at the unit is leak free and the manual shutoff is accessible

Section 9 of 10 · 5 questions

Electrical And Controls

  1. The roof service disconnect is labeled, weather-tight, and operates cleanly

  2. Contactors and relays are free of pitting, welding, and heat discoloration

  3. Run and start capacitors measure within tolerance of their nameplate rating

  4. High and low pressure switches and the freeze stat operate at their set values

  5. Active fault codes on the unit controller are recorded and cleared after resolution

Section 10 of 10 · 5 questions

Performance Verification

  1. Return air and supply air temperatures at the unit

  2. Compressor and fan motor amp draw on each phase

  3. Measured amp draw is within nameplate limits for the compressor and each motor

  4. Each cooling stage loads and unloads in sequence without short cycling

  5. The occupied and unoccupied schedule on the controller matches actual building use

Checklist by GoAudits. This checklist is an example: we do not guarantee compliance with the laws applicable to your territory or industry. Seek professional advice to adapt it to your workplace or jurisdiction.

Free PDF

Download the RTU Maintenance Checklist for Rooftop Units

By downloading this checklist you agree to the GoAudits privacy policy and terms of service.

NEW! Try generating a custom checklist with our free AI tool:

Easy inspection app for your digital checklists