IEC 61439 Checklist

Use the IEC 61439 Checklist to verify low-voltage switchgear and control gear assemblies meet marking, enclosure, wiring, protective circuit, and routine verification requirements before energization.

IEC 61439 Checklist



Documentation And Marking

1. The assembly nameplate is present, legible, and fixed to the enclosure.


Photo Comment

2. The nameplate includes the manufacturer's name, type designation, and serial number.


Photo Comment

3. Rated voltage, rated current, rated frequency, and rated short-circuit withstand current (Icw) are marked on the assembly.


Photo Comment

4. The degree of protection (IP rating) is marked on the enclosure.


Photo Comment

5. The form of internal separation is marked or documented where specified.


Photo Comment

6. CE marking is present on the assembly where required for the EU market.


Photo Comment

7. The assembly is accompanied by a technical file or declaration of conformity from the original manufacturer.


Photo Comment

8. A circuit diagram or single-line diagram is present, matches the installed assembly, and is retained with the unit.


Photo Comment

9. Operation and maintenance documentation is available and handed over to the responsible party.


Photo Comment
Enclosure And Mechanical Condition

1. The enclosure is free from physical damage, dents, corrosion, and paint defects.


Photo Comment

2. All enclosure doors, covers, and panels open, close, and latch correctly.


Photo Comment

3. Door seals and gaskets are intact and free from damage or gaps.


Photo Comment

4. Cable entry points are sealed with appropriate glands or blanking plates; no open knockouts are present.


Photo Comment

5. The IP rating of the enclosure is maintained at all cable entry and exit points.


Photo Comment

6. Ventilation openings are unobstructed and correctly fitted with grilles or filters where specified.


Photo Comment

7. Internal separation barriers and partitions are correctly installed and undamaged where a Form 2b or higher separation is specified.


Photo Comment

8. All internal components are correctly mounted, aligned, and secured.


Photo Comment
Busbars And Internal Connections

1. Busbars are the correct size and material per the assembly design documentation.


Photo Comment

2. Busbar supports and insulators are correctly installed at the specified intervals and free from damage.


Photo Comment

3. All busbar connections and joints are correctly torqued and free from signs of overheating or corrosion.


Photo Comment

4. Creepage distances and clearances between live parts and between live parts and earth meet the requirements for the rated voltage.


Photo Comment

5. Phase identification markings on busbars are present and consistent throughout the assembly.


Photo Comment

6. The neutral busbar is correctly sized and installed per the assembly design.


Photo Comment

7. The protective earth (PE) busbar is present, correctly rated, and connected to the enclosure.


Photo Comment
Wiring And Cable Terminations

1. All internal wiring is the correct type, rating, and color coding per the assembly drawings and applicable standards.


Photo Comment

2. Wiring is correctly routed, supported, and free from damage, chafing, or sharp edges.


Photo Comment

3. All terminal connections are tight and correctly torqued; no loose or missing connections are present.


Photo Comment

4. All wire ends are correctly ferrulled and labeled at both ends to match the circuit diagram.


Photo Comment

5. No wire ends are left unconnected or unterminated within the assembly.


Photo Comment

6. Control wiring is segregated from power wiring where required by the design.


Photo Comment

7. Cable entries from external circuits are correctly terminated and cables are supported at the point of entry.


Photo Comment
Protective Circuits And Earthing

1. The protective earth (PE) busbar is connected to the enclosure and to all exposed conductive parts within the assembly.


Photo Comment

2. Continuity of the protective circuit is confirmed; resistance between the enclosure and each earth terminal does not exceed 0.05 ohms.


Photo Comment

3. All equipment earth terminals within the assembly are connected to the PE busbar.


Photo Comment

4. Earth connections are free from paint, corrosion, or insulating material at the contact points.


Photo Comment

5. The protective conductor cross-section meets the minimum requirement for the associated phase conductor size.


Photo Comment
Component Installation And Ratings

1. All installed components (circuit breakers, contactors, fuses, relays, meters) match the type and rating specified on the assembly schedule or circuit diagram.


Photo Comment

2. Components are correctly mounted in their designated positions per the assembly drawings.


Photo Comment

3. All circuit breakers and isolators are correctly seated and latched.


Photo Comment

4. Fuse ratings and types match the circuit schedule; no incorrect or mismatched fuses are installed.


Photo Comment

5. Overload relay settings are verified against the connected load ratings.


Photo Comment

6. Interlocks (mechanical and electrical) operate correctly and prevent unsafe switching combinations.


Photo Comment

7. All pilot lights, push buttons, and selector switches are operational and correctly labeled.


Photo Comment

8. Meters and measuring instruments are connected to the correct circuits and displaying readings within expected ranges.


Photo Comment
Routine Verification Tests

1. Insulation resistance is measured between all live conductors and earth with all circuit breakers in the ON position and sensitive devices disconnected; readings are recorded and meet the minimum required value.


Photo Comment

2. Dielectric withstand test (or insulation resistance as an alternative) is conducted at the specified test voltage and duration; no breakdown or flashover occurs.


Photo Comment

3. Continuity of protective circuits is confirmed by test for each earth path and results are recorded.


Photo Comment

4. Mechanical operation of all circuit breakers, isolators, and switching devices is verified; all operate smoothly without binding.


Photo Comment

5. All interlocks are tested and confirmed operational.


Photo Comment

6. Correct operation of all indicators, alarms, and control circuits is verified.


Photo Comment

7. All routine test results are recorded in a test report retained with the assembly documentation.


Photo Comment
Handover And Acceptance

1. The assembly matches the specification, purchase order, and approved drawings in all material respects.


Photo Comment

2. All routine test certificates from the assembly manufacturer are present and reviewed.


Photo Comment

3. Outstanding defects, deviations, or non-conformances are documented and agreed actions are recorded.


Photo Comment

4. The assembly is confirmed ready for installation and energization with no open safety-critical defects.


Photo Comment

5. Documentation package (circuit diagrams, test reports, operation manuals, declaration of conformity) is complete and handed over to the site or facilities team.


Photo Comment

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.

Is this sample what you are looking for?
Sign up to use & customize this template, or create your own custom checklist.

NEW! Try generating a custom checklist with our free AI tool:

Easy inspection app for your digital checklists