Food Truck Inspection Checklist

Use this Food Truck Inspection Checklist to assess food truck equipment, sanitation, and safety standards, ensuring safe food preparation for customers.

Food Truck Inspection Checklist



Exhaust Hood

1. Is cooking equipment that produces grease-laden vapors protected by a type I commercial kitchen exhaust hood? (IFC 319.1)


Photo Comment

2. Does the ventilation system operate at the required rate of air movement? (IFC 607.3.1)


Photo Comment

3. Are UL 1046 grease filters installed and clean? (IFC 607.3.1 & 607.3.3)


Photo Comment

4. Has the exhaust hood been inspected and cleaned, and is the proper tag or label affixed to the hood? (IFC 607.3.3.3)


Photo Comment
Fire Protection For Cooking Equipment

1. Is the exhaust hood equipped with a fire suppression system? (IFC 319.4.1 & 904.2.2)


Photo Comment

2. Is the system free of damage and operable? (NFPA 17A)


Photo Comment

3. Is a manual means of activation present? (IFC 904.3.2)


Photo Comment

4. Is an automatic means of activation present? (IFC 904.3.2)


Photo Comment

5. Is an automatic fuel shutoff installed and functional? (IFC 904.3.3)


Photo Comment

6. Is an automatic electrical shutoff installed and functional? (IFC 904.3.3)


Photo Comment

7. Are the system discharge nozzles directed at the proper cooking surface? (NFPA 17A)


Photo Comment

8. Are protective caps in place on all discharge nozzles? (NFPA 17A)


Photo Comment

9. Has the system been inspected and tested within the last 6 months? (IFC 904.5.1)


Photo Comment

10. Is current inspection and testing documentation or tagging present? (IFC 904.5)


Photo Comment
Fire Extinguishers

1. Is a Class K fire extinguisher present for suppression of cooking fires? (IFC 906.4)


Photo Comment

2. Is there a minimum of one 2A10BC fire extinguisher for ordinary combustibles and flammable liquids? (IFC 319.4.2 & 906.3)


Photo Comment

3. Are all fire extinguishers mounted in conspicuous, unobstructed locations? (IFC 906.5 & 906.6)


Photo Comment

4. Has a monthly visual inspection been performed by the vehicle owner? (NFPA 10)


Photo Comment

5. Has an annual inspection been performed by a qualified individual or contractor? (NFPA 10)


Photo Comment

6. Are inspection tags on fire extinguishers current and properly attached? (NFPA 10)


Photo Comment
Appliance Connection To Fuel Supply

1. Are gas cooking appliances secured in place to prevent movement? (IFC 319.5)


Photo Comment

2. Are gas appliances connected to fuel-supply piping using an ANSI Z21.69/CSA 6.16 listed connector? (IFC 319.5)


Photo Comment

3. Are movement restraining devices installed on gas appliances to prevent disconnection or stress on fuel lines? (IFC 319.5)


Photo Comment

4. Are shutoff valves on all gas cylinders readily accessible? (NFPA 58: 6.26.4.1)


Photo Comment

5. Are gas-fired heating appliances and water heaters equipped with automatic shutoff devices that stop gas flow to the main burner and pilot if the pilot flame is extinguished? (NFPA 58: 6.26.7.11)


Photo Comment

6. Are regulators installed in accordance with NFPA 58 Section 6.26.4.2 (A) through (E)?


Photo Comment

7. Is piping installed in accordance with NFPA 58 Section 6.26.5.1 (A) through (M)?


Photo Comment

8. Are gas cylinders stamped with the required approval and testing information? (NFPA 58: 5.2.1.1)


Photo Comment

9. Is the entire fuel system free of leaks? (NFPA 58: 6.16)


Photo Comment

10. Are full-system leak testing documents available for piping and appliance connections? (NFPA 58: 6.26.5.1)


Photo Comment

11. Are LP gas valves shut off when appliances are not in use? (NFPA 58: 6.26.8.3)


Photo Comment

12. Is a permanent caution plate affixed to the appliance or vehicle displaying the required NFPA 58: 6.26.7.10 safety instructions?


Photo Comment

13. Is a listed LP gas alarm present and installed? (IFC 319.8.5)


Photo Comment

14. Has fuel gas piping been inspected and labeled by an approved agency within the last year?  (IFC 319.10.3)


Photo Comment

15. Have LP gas containers been inspected and labeled by an approved agency within the last year if required by the AHJ? (IFC 319.10.3)


Photo Comment
CNG (Compressed Natural Gas) System Safety

1. Is CNG used only for cooking and not for vehicle propulsion? (NFPA 52)


Photo Comment

2. Is the maximum aggregate capacity of CNG cylinders 1,300 lbs or less? (IFC 319.9.1.1)


Photo Comment

3. Is CNG stored in NGV-2-type cylinders? (IFC 319.1.3)


Photo Comment

4. Are CNG cylinders securely mounted in a location protected from direct vehicle impact? (IFC 319.9.2)


Photo Comment

5. Is CNG piping, including valves and fittings, protected from tampering, impact, and vibration damage? (IFC 319.9.3)


Photo Comment

6. Is a listed methane gas alarm installed? (IFC 319.9.4)


Photo Comment

7. Has CNG fuel gas piping been inspected and labeled by an approved agency within the last year if required by the AHJ? (IFC 319.10.3)


Photo Comment

8. Have CNG containers been inspected and labeled by a qualified service facility within the last 3 years if required by the AHJ? (IFC 319.10.3)


Photo Comment

9. Are CNG containers within their expiration date as listed on the container label? (IFC 319.10.3)


Photo Comment
General Safety

1. Is the area free from excessive trash and other combustible materials that may obstruct egress? (IFC 304.1.1)


Photo Comment

2. Are combustible materials stored in an approved manner and kept away from ignition sources? (IFC 305.1)


Photo Comment

3. Are appliances located so a fire at any appliance will not block occupants' egress from the vehicle? (NFPA 58: 6.26.7.7)


Photo Comment

4. Are appliances constructed or protected to minimize damage or impairment due to cargo shifting or handling? (NFPA 58: 6.26.7.8)


Photo Comment

5. Do generators not pose a hazard to the public? (IFC 313.1.1)


Photo Comment

6. Is the generator adequately fueled to last for the duration of the event without needing to be refueled during operation? (IFC 313.1.1)


Photo Comment

7. Is the parked vehicle positioned so that it does not obstruct the fire apparatus access road? (IFC 503.4)


Photo Comment

8. Is unobstructed access to fire hydrants maintained? (IFC 507.5.4)


Photo Comment

9. Do all power taps and multiplug adapters comply with NFPA 70 / NEC standards? (IFC 604.4 & NEC 400.10)


Photo Comment

10. Are flexible extension cords listed/labeled, free of damage, and located away from public areas? (IFC 604.5)


Photo Comment
Cooking Oil Storage – Metallic Tanks

1. Is a UL 80 or UL 142 listed tank used for cooking oil storage? (IFC 319.7.1)


Photo Comment

2. Is the tank installed per the manufacturer’s instructions? (IFC 319.7.1)


Photo Comment

3. Are piping, valves, fittings, hoses, and related components suitable for expected operating pressures, temperatures, and stresses? (IFC 319.7.3 & 319.7.4)


Photo Comment

4. Is normal and emergency venting installed above the oil tank fill line? (IFC 319.7.5)


Photo Comment
Cooking Oil Storage – Non-Metallic Tanks

1. Does the total capacity of non-metallic cooking oil tanks not exceed 200 gallons? (IFC 319.7.2)


Photo Comment

2. Is the non-metallic tank listed for the storage of cooking oil? (IFC 319.7.2)


Photo Comment

3. Are piping, valves, fittings, hoses, and related components suitable for expected operating pressures, temperatures, and stresses? (IFC 319.7.3 & 319.7.4)


Photo Comment

4. Is normal and emergency venting installed above the oil tank fill line? (IFC 319.7.5)


Photo Comment
Cooking Oil Storage – Individual Containers

1. Does the aggregate total of individual oil containers not exceed 120 gallons? (IFC 319.6)


Photo Comment

2. Are individual containers stored in a manner that prevents toppling or damage during transport? (IFC 319.6)


Photo Comment
LP Fuel For Cooking

1. Is the vehicle free from indoor operation while LP gas is onboard? (NFPA 58: 9.7.3.6)


Photo Comment

2. Are LP gas containers installed outside the vehicle or in an exterior-vented cabinet that is vapor-tight to the interior? (NFPA 58: 6.26.3.3)


Photo Comment

3. Are LP gas cylinders adequately filled to sustain the event without needing refilling during operation?


Photo Comment

4. Does the total LP gas capacity not exceed 200 lbs.? (IFC 319.8.1)


Photo Comment

5. Are LP gas cylinders securely mounted to the vehicle? (IFC 319.8.2)


Photo Comment

6. Is the fixed piping system equipped with two-stage regulation? (NFPA 58)


Photo Comment

7. Are regulator vent outlets at least 2 inches above the compartment vent opening? (NFPA 58: 6.26.3.3)


Photo Comment

8. Is LP piping, including valves and fittings, protected against tampering, impact, and vibration damage? (IFC 319.8.4)


Photo Comment

Is this sample what you are looking for?
Sign up to use & customise this template, or create your own custom checklist:

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.

Easy inspection app for your digital checklists