Solar Commissioning Checklist

Use this Solar Commissioning Checklist template to verify installation and that all components of the solar PV system operate effectively and safely.

Solar Commissioning Checklist



AC Combiner Panel

1. Is field wiring neatly routed inside the box?


Photo Comment

2. Are field wiring terminations tight?


Photo Comment

3. Is field wiring properly polarity marked with colored tape or jacket color?


Photo Comment

4. Is wire identified with permanent markers/labels?


Photo Comment

5. Is the ground wire securely attached?


Photo Comment

6. Do fuse types and ratings conform to the one-line diagram (when used)?


Photo Comment

7. Are fuses installed (when used)?


Photo Comment

8. Are conduit connections tight and are bushings used if applicable?


Photo Comment

9. Are labels in place and do they conform to the values?


Photo Comment

10. Does the combiner rating conform to the one-line diagram?


Photo Comment

11. Is the box properly accessible and lockable?


Photo Comment

12. Is the box cover secure and tight?


Photo Comment

13. Is a locking seal installed if readily accessible?


Photo Comment
AC Disconnect Switch

1. Is field wiring neatly routed inside the box?


Photo Comment

2. Are field wiring terminations tight?


Photo Comment

3. Is field wiring properly polarity marked with colored tape or jacket color?


Photo Comment

4. Is wire identified with permanent markers/labels?


Photo Comment

5. Is the ground wire securely attached?


Photo Comment

6. Do fuse types and ratings conform to the one-line diagram (when used)?


Photo Comment

7. Are fuses installed (when used)?


Photo Comment

8. Are conduit connections tight and are bushings used if applicable?


Photo Comment

9. Are labels in place and do they conform to the values?


Photo Comment

10. Does the disconnect rating conform to the one-line diagram?


Photo Comment

11. Is the box properly accessible and lockable?


Photo Comment

12. Is the box cover secure and tight?


Photo Comment

13. Is a locking seal installed?


Photo Comment
KWh Meter

1. Are all wire connections tight?


Photo Comment

2. Is field wiring properly polarity marked with colored tape or jacket color?


Photo Comment

3. Is the ground wire securely attached (equipment ground)?


Photo Comment

4. Are conduit connections tight and are bushings used if applicable?


Photo Comment

5. Is the meter labeled as a solar array meter?


Photo Comment

6. Is the box cover secure and tight?


Photo Comment

7. Is the neutral not bonded to ground in customer-owned equipment?


Photo Comment

8. Is the kWh reading recorded on the second register if applicable?


Photo Comment
Service Panel

1. Are labels in place?


Photo Comment

2. Is there a label to identify the breaker and to indicate not to relocate?


Photo Comment
Inverter 1

1. Are working and ventilation clearances as per the manufacturer's specifications?


Photo Comment

2. Is polarity correct for inverter connections?


Photo Comment

3. Has the grounding electrode conductor been confirmed to land on the inverter where the manufacturer requires it?


Photo Comment

4. Is the grounding electrode conductor not choked?


Photo Comment

5. Is the grounding electrode conductor used only with irreversible connections?


Photo Comment

6. Is the inverter's time and date set correctly?


Photo Comment

7. Have the model number and serial number of the inverter been recorded?


Photo Comment

8. Does the inverter location number match that of the three-line diagram?


Photo Comment

9. Is there a warning label about "if a ground fault is indicated…"?


Photo Comment

10. Is there a label with the date of installation?


Photo Comment

11. Is there a label with a sticker containing the service phone number?


Photo Comment
Data Acquisition System

1. Is the network connection confirmed?


Photo Comment

2. Has the serial number of the data logger been recorded?


Photo Comment

3. Is the irradiance meter installed at the same plane as the array?


Photo Comment

4. Is the irradiance meter extension wire type K as per the manufacturer’s recommendations?


Photo Comment

5. Is the device name set as: “Inv # MFG Model# S/N” (e.g., Inv1 Satcon PVI50 JAK0827341)?


Photo Comment

6. Is the location of the breaker/switch that feeds the logger labeled and recorded?


Photo Comment
Application Notes

1. Have all notes on electrical drawings been confirmed?


Photo Comment

2. Have all notes on mechanical drawings been confirmed?


Photo Comment
Site

1. Is the site clean and is all waste removed?


Photo Comment
Electrical Checkout

1. Is the megohm reading from the utility interconnection disconnect to the external utility disconnect greater than 20M ohms in 1 minute?


Photo Comment

2. Is the megohm reading from the external utility disconnect to the inverter service disconnect greater than 20M ohms in 1 minute?


Photo Comment

3. Is the megohm reading from the inverter DC service disconnect to the array disconnect recorded for the following? What is their 1 min value? * Ungrounded conductor * Grounded conductor if easily lifted


Photo Comment

4. Is the megohm reading from the array disconnect to the fused combiner recorded for the following? What is their 1 min value? * Ungrounded conductor * Grounded conductor if easily lifted


Photo Comment
AC Circuits Before Turn On

1. Is the proper AC voltage verified at the AC disconnect?


Photo Comment

2. What is the value of Lines 1 to Neutral?


Photo Comment

3. What is the value of Lines 2 to Neutral?


Photo Comment

4. What is the value of Lines 3 to Neutral?


Photo Comment

5. What is the value of Lines 1 to 2?


Photo Comment

6. What is the value of Lines 2 to 3?


Photo Comment

7. What is the value of Lines 3 to 1?


Photo Comment

8. What is the value of the phase rotation?


Photo Comment

9. Is the system turned on for the following tests? Temperature Sky Conditions Wind Speed Horizontal Irradiance


Photo Comment

10. What is the total PV amps (sum of all inputs)?


Photo Comment

11. What is the MPP voltage in volts recorded?


Photo Comment

12. What is the total DC input power (volts times amps, not inverter display) recorded in watts?


Photo Comment

13. What is the inverter output reading in watts recorded?


Photo Comment

14. Is the inverter efficiency (DC power/AC power) greater than 90%?


Photo Comment
PV Modules And Module Wiring

1. Have MC connections been inspected for workmanship?


Photo Comment

2. Are module cables properly secured to the module frame with no dangling wires?


Photo Comment

3. Is the bend radius no greater than four times the diameter of the wire?


Photo Comment

4. Is there no debris on the module surface, such as foam pads or sealant residue?


Photo Comment

5. Is there no physical damage to module frames or laminates?


Photo Comment

6. Does module wiring enter a strain relief prior to landing on any terminal block?


Photo Comment

7. Is the ground wire and lug securely attached to the rails and to module frames?


Photo Comment

8. For the Array GEC connection, is the wire size, wire support, and wire type compliant with the 2008 code?


Photo Comment

9. Is the string layout marked up on the array layout and recorded?


Photo Comment

10. Have the serial numbers been recorded?


Photo Comment
Data Acquisition

1. Does the irradiance reading match that of the handheld unit within +/-5%?


Photo Comment

2. Does the cell temperature reading match that of the handheld unit within +/-5%?


Photo Comment

3. Does the ambient temperature reading match that of the handheld unit within +/-5%?


Photo Comment

4. Can each inverter be read on the DAS website?


Photo Comment

5. Does the sum of inverter power outputs on the DAS match the revenue-grade kWh meter output within +/-2%?


Photo Comment

6. Is power production correctly polarized?


Photo Comment

7. Does each inverter read appropriate power?


Photo Comment

8. Is the DAS power reading in watts recorded?


Photo Comment

9. Is the inverter power reading in watts recorded?


Photo Comment

10. Is the inverter vs. DAS reading within 7%?


Photo Comment

11. Are inverters shown on the DAS Asset Details with Inv#, MFG, model number, and SN?


Photo Comment

12. Has the time taken for the inverter to reconnect after an AC loss been recorded?


Photo Comment
Mounting Hardware

1. Is all hardware installed as designed and torqued as needed?


Photo Comment

2. Is the correct hardware stack-up confirmed, such as lock washers where needed?


Photo Comment

3. Are roof penetrations secured and flashed?


Photo Comment

4. Is the racking properly secured to rafters or standing seams?


Photo Comment

5. Does the ballasting plan conform to the manufacturer’s compliance letter?


Photo Comment
Building Envelope Penetrations

1. Are all penetrations weather-sealed or fire-stopped around the outside of conduits?


Photo Comment

2. Are all conduit raceways filled with duct seals at the first building penetration?


Photo Comment

3. Are signal wiring penetrations (DAS) sealed around the outside of conduits?


Photo Comment

4. Is "DC Voltage Warning" labeled on DC conduits?


Photo Comment
DC Source Circuit Junction Box

1. Is the box securely fastened and sealed against the weather, with weep holes if needed?


Photo Comment

2. Is the array wiring leading to the box neat and supported?


Photo Comment

3. Is field wiring routed neatly within the box?


Photo Comment

4. Are field wiring terminations tight?


Photo Comment

5. Is field wiring properly polarity marked with colored tape or wire insulation color?


Photo Comment

6. Is wire identified with permanent markers/labels (e.g., string numbers)?


Photo Comment

7. Is the ground wire securely attached?


Photo Comment

8. Are conduit connections tight and are bushings used if applicable?


Photo Comment

9. Is a drip loop incorporated into the wiring as it enters the box?


Photo Comment

10. Are locations marked on the roof layout or conduit drawing?


Photo Comment

11. Are conductors rated for the location (e.g., THWN-2)?


Photo Comment

12. Is there a "Warning: DC Voltages" label?


Photo Comment
Source Circuit Fused Combiner Box

1. Is the box securely fastened and sealed against the weather?


Photo Comment

2. Is field wiring routed neatly within the box?


Photo Comment

3. Are field wiring terminations tight?


Photo Comment

4. Is field wiring properly marked with colored tape or jacket color for polarity?


Photo Comment

5. Is wire identified with permanent labels (e.g., String# one side)?


Photo Comment

6. Is the ground wire securely attached?


Photo Comment

7. Does the fuse combiner type and rating conform to the one-line diagram?


Photo Comment

8. Are conduit connections tight and are bushings used if applicable (e.g., Myers)?


Photo Comment

9. Is a drip loop incorporated into the wiring as it enters the box?


Photo Comment

10. Is the box cover secure and tight?


Photo Comment

11. Are locations marked on the roof layout or conduit drawing?


Photo Comment

12. Is the combiner labeled to show which inverter or switch it goes to, and does it conform to the three-line diagram?


Photo Comment

13. Is there a warning label indicating not to remove fuses under load and noting the presence of DC voltages?


Photo Comment
DC Disconnect Switch

1. Is field wiring neatly routed inside the box?


Photo Comment

2. Are field wiring terminations tight?


Photo Comment

3. Is wire identified with permanent markers/labels?


Photo Comment

4. Are fuses installed (when used)?


Photo Comment

5. Do fuse types and ratings conform to the one-line diagram (when used)?


Photo Comment

6. Is the ground wire securely attached?


Photo Comment

7. Are conduit connections tight and are bushings used if applicable?


Photo Comment

8. Is the box cover secure and tight?


Photo Comment

9. Does the rating conform to the one-line diagram?


Photo Comment

10. Are labels in place and do they conform to the values?


Photo Comment

11. Is a locking seal installed if readily accessible?


Photo Comment