Monthly Legionella Audit

A checklist to monitor your water system and ensure compliance with health and safety guidelines related to legionella. Use this digital checklist for regular record keeping, to produce a water logbook as part of your legionella risk assessment plan.

Monthly Legionella Audit



Legionella Checks

1. Cold water tanks are checked every 6 months (must be below 20 degrees celsius).


Photo Comment

2. Annual inspection of cold water tanks is completed.


Photo Comment

3. Monthly checks of flow and return to hot storage tanks (flow must be 60 or above, return must be 50 or above).


Photo Comment

4. Monthly checks of the hot and cold taps nearest and furthest away from each storage tank.


Photo Comment

5. Monthly water temperature checks (hot must be <42, cold must be <20.


Photo Comment

6. Weekly purge of dead legs.


Photo Comment

7. Weekly purge of little or unused outlets.


Photo Comment

Is this sample what you are looking for?
Sign up to use & customise this template, or create your own custom checklist:

Checklist by GoAudits.com – Please note that this checklist is intended as an example. We do not guarantee compliance with the laws applicable to your territory or industry. You should seek professional advice to determine how this checklist should be adapted to your workplace or jurisdiction.